Gas boiler backup power: output and battery capacity
Estimate the energy needed for controls and a pump, and learn which compatibility checks need separate attention.
Use the boiler’s electrical consumption
A boiler’s heat output in kW is not its electrical consumption. Battery planning needs the electrical demand of its controls, fan and pump. Find this in the manual or measure it. Do not count the built-in pump twice if it is already included in the boiler’s electrical rating.
An 8-hour example
A constant 120 W load over 8 hours uses 960 Wh. At 85% efficiency, that requires at least 1,130 Wh of nominal battery capacity. If the boiler cycles, adjust the active-time percentage. Add other devices in the full calculator.
Check electrical compatibility separately
A Wh calculation does not confirm that a particular boiler will start. Check waveform, startup power, neutral and earthing requirements in the manufacturers’ documentation. A qualified electrician should assess compatibility and connections to household wiring. Never use a male-to-male cable.